Type No.:MAG-35kV load break elbow THE-35
35kV underground elbow connectors provide utilities with products having high reliability and low maintenance expense.
These connectors provide:
Standard elbow and bushing loadbreak principle
Molded shields
Peroxide-cured EPDM compounds
Purple cuffs for quick 35kV identification
The separable elbow connector is designed for use with single-conductor, concentric neutral power cable having extruded
insulation shielding. With shield adapter products, the elbow can be used with cables having a metallic tape shield,
wire shield, or lead sheath with tape or extruded insulation shielding.
All insulating and conducting rubber components are made of a special formulation of an EPDM elastomer using a
peroxide curing process. The material and curing process provide's superior elastomer stress relaxation characteristics under
high ambient temperatures and contributes to reliable, long-time operation in either above-ground or subsurface installations.
Elbow connector/integral bushing combinations are suitable for energized loadmake/loadbreak operations by a qualified
lineman using an shotgun-type hot stick. All elbow/integral bushing combinations are designed for use with subsurface or
padmounted installations.
35 kV LOADBREAK PRODUCTS
RATINGS & SPECIFICATIONS
GENERAL INFORMATION
35 kV loadbreak elbows are designed for operation on and connection to 35 kV class, 150 kV BIL systems where the voltage
ratings listed on this page are not exceeded.
Where To Use
Max. Continuous Voltage................ phase-to-ground:21.1 kV
phase-to-phase:36.6 kV
Continuous Current......................... 200 ampere rms
RATINGS
0.17-Second Duration..................... 10,000 amperes rms symmetrical
3.00-Second Duration..................... 3500 amperes rms symmetrical
SHORT-TIME CURRENT RATINGS
INSULATION WITHSTAND VOLTAGES
Basic Impulse Level........................ 150 kV crest
DC (15 minutes).............................. 104 kV
Corona Extinction Voltage............... 26 kV rms
phase and 3-phase circuits, 10 loadmake/loadbreak 21.1 kV phase-to-ground, operations at 200 amperes
36.6 kV maximum
SWITCHING
SELECTION AND ORDERING
Cat
Number
 
Conductor Cross
section mm2
Outer diameter
for conductor mm
THE-35/200-35
THE-35/200-50
THE-35/200-70
THE-35/200-95
THE-35/200-120
35
50
70
95
120
20.96-25.40
25.27-29.97
25.27-29.97
29.97-34.04
29.97-34.04
Elbow must be sized to the cable insulation diameter.
Select the elbow according the cable outer dimension.